A leading women's oncology centre in Defence Colony, New Delhi required a validated UV disinfection system for drinking water supply, meeting NABH HIC 3.1 infection-control standards with a PLC-monitored SS316L electropolished unit.
Project at a glance
15,000 LPH SS316L electropolished UV water disinfection system, 3 × Philips 55W TUV lamps, 40 mJ/cm², PLC auto-alarm panel, installed at a Delhi oncology hospital — NABH HIC 3.1 and BIS IS 10500 compliant.
The Challenge
India's healthcare sector operates over 70,000 registered hospitals, with the country's major cities — Delhi, Mumbai, Chennai — hosting the highest concentration of tertiary and specialty care centres. The National Accreditation Board for Hospitals (NABH) mandates infection-control standards that include verifiable microbiological safety of water supplied to patient-contact areas. For cancer hospitals and immunocompromised patient wards, the Indian Public Health Association and Ministry of Health guidelines classify drinking water as a critical infection-control resource, subject to documentation at every stage of treatment and distribution.
Oncology hospitals face the most demanding water quality environment in Indian healthcare. Immunocompromised patients undergoing chemotherapy or radiation therapy are acutely vulnerable to opportunistic pathogens — Pseudomonas aeruginosa, Legionella, and Cryptosporidium — that healthy individuals can tolerate. Even trace concentrations of these organisms in hospital drinking water can trigger life-threatening infections. NABH HIC 3.1 (Hospital Infection Control) standards require documented terminal disinfection with validated dose records, and biomedical audits specifically check that the UV system is operating within its rated dose range.
The oncology centre's existing UV system was undersized for the facility's expanded patient capacity, used an older SS304 chamber not rated for electropolishing, and lacked a PLC-based alarm system to alert facility engineers in real time if lamp intensity dropped below the minimum 40 mJ/cm² germicidal threshold. With NABH accreditation renewal approaching, the biomedical engineering team required a complete system replacement that would meet NABH HIC 3.1, BIS IS 10500 potable water standards, and Schedule M 2025 pharmaceutical-grade construction guidelines — not merely a lamp swap.
The Solution
Alpha UV's IIT Patna-trained engineers conducted a site assessment at Defence Colony, reviewing the hospital's water demand profile, distribution architecture, and NABH audit documentation requirements. The engineering team sized the replacement system at 15,000 LPH — matching the facility's expanded operational water demand across patient wings, cafeteria, and service areas — with a 20% hydraulic safety margin to prevent dose shortfall during peak morning draw.
Alpha UV installed an electropolished SS316L UV disinfection system at 15,000 LPH — an electropolished SS316L stainless steel chamber (the highest-grade construction specified in Schedule M 2025 for pharmaceutical and medical water contact) fitted with 3 × Philips 55W TUV UV-C lamps operating at the germicidal 254nm wavelength. The system delivers a validated minimum UV dose of 40 mJ/cm² at the rated 15,000 LPH flow with a water UVT of 95%, exceeding the NSAI/WHO recommended 25 mJ/cm² minimum for drinking water disinfection by a factor of 1.6×. The PLC auto-alarm panel continuously monitors UV intensity via a calibrated sensor and triggers an audible and visual alarm — routed to the biomedical engineering station — if intensity falls below the minimum threshold. 2-inch flanged SS316L inlet/outlet connections integrate directly into the hospital's existing distribution pipework.
The electropolished SS316L chamber interior eliminates surface roughness that can harbour biofilm or trap particulates in medical water systems. This construction standard is critical in a hospital setting where equipment surfaces are subject to periodic CIP (clean-in-place) protocols and must withstand repeated passivation cycles without corroding or releasing heavy metal ions into the water supply.
Alpha UV supplied a complete NABH-ready documentation package at system commissioning: UV dose calculation report signed by a qualified engineer, Philips TUV lamp Certificate of Analysis (COA), SS316L material test certificate, PLC alarm calibration record, BIS IS 10500 compliance statement, and a preventive maintenance schedule for the hospital's biomedical equipment file. The documentation package is formatted for direct insertion into the NABH HIC 3.1 audit binder.
Technical Details
Results
Before / After
| Parameter | Before UV Treatment | After UV Treatment | Regulatory Standard |
|---|---|---|---|
| Total Coliform | 12 CFU/100 mL | < 1 CFU/100 mL | BIS IS 10500: 0 CFU/100 mL |
| E. coli | 3 CFU/100 mL | Not detected | BIS IS 10500: 0 CFU/100 mL |
| Pseudomonas aeruginosa | Detected | Not detected | NABH HIC 3.1: 0 CFU/100 mL |
| UV Dose Delivered | 18 mJ/cm² (old system) | 40 mJ/cm² | WHO: ≥ 25 mJ/cm² |
| Turbidity | 0.4 NTU | 0.4 NTU (unchanged) | BIS IS 10500: ≤ 1 NTU |
"The UV dose calculation report, Philips COA, and NABH-formatted documentation meant we sailed through the biomedical audit. The PLC alarm gives our engineering team complete confidence between maintenance cycles."
— Head of Biomedical Engineering, Oncology Hospital, New Delhi
Next Steps
Similar application?
Get a quote in 24 hours. Tell us your flow rate, application, and location.
Get a Quote on WhatsAppExplore Hospital UV Disinfection Systems
Technical specifications, UV dose data, compliance standards, and product options for this application.
View Application PageMore Case Studies
Mon–Sat · 9 AM–6 PM IST · IIT Patna alumni on call
IIT Patna-engineered. Philips UV-C powered. Tell us your application and we'll respond within 2 hours.
+91 93183 05878
Get Quote →
Call Direct
+91 95995 00580
Tap to Call →
Send Enquiry
Detailed specifications form
Open Form →